I have a couple of questions about the T104 timers.
Currently there is a 20 amp 240v circuit for the lights. The circuit terminates at 4 6-20R receptacles. There will only be two 600w 240v hps ballasts run off it for now, with the possible addition of another couple 600w or a 400w down the line.
Before I have seen the T104 ran so that the wire coming from the breaker goes into the T104, then that goes out to the receptacles, so that you have timed receptacles. Is it possible to wire it so that the incoming wire on the T104 plugs into one of the 6-20R receptacles, and then two wires are hardwired on the outgoing side from the T104 to the ballasts?
The only problem I am seeing is that the wire would then be stranded instead of solid going into and out of the T104. Is that ok?
Is this a safe setup?
Currently there is a 20 amp 240v circuit for the lights. The circuit terminates at 4 6-20R receptacles. There will only be two 600w 240v hps ballasts run off it for now, with the possible addition of another couple 600w or a 400w down the line.
Before I have seen the T104 ran so that the wire coming from the breaker goes into the T104, then that goes out to the receptacles, so that you have timed receptacles. Is it possible to wire it so that the incoming wire on the T104 plugs into one of the 6-20R receptacles, and then two wires are hardwired on the outgoing side from the T104 to the ballasts?
The only problem I am seeing is that the wire would then be stranded instead of solid going into and out of the T104. Is that ok?
Is this a safe setup?