Then hook up two separate outlets using one hot leg on each and the ground - one for your two 1K's and one for your three 300w to try and balance the load going through the 240v breaker.
It would be a good idea to replace the 240v breaker with two 20 amp 120v breakers for safety if you have #12 wire, you can go 30 amp if you have #10 wire (Which is probably is).
Where is the neutral going to come from? If it's just 2 hots and a ground, then you have to switch things around back in the panel to get 120v)
Actually, it could be potentially fatal to switch out a double pole with 2 single poles. 210.4(B)
You are correct. But he does have 120v right there at the receptacle between one of the hots and the neutral/ground; however, he would be lacking a seperate ground. You are also right in that he can't use the neutral in common with both phases. I shouldn't give advice when stoned!
So then the easiest solution for him to be just to use one of the existing wires for hot, one for neutral, one for ground and change it back at the panel through a 30 amp breaker????
I am not sure what you're getting at here? Pulling out the double pole and using the space to throw in two single poles for two separate circuits shouldn't be a hazard.
When working with a 10/3 as 2 separate circuits using a shared neutral, both ungrounded conductors need to be simultaneously disconnected in the case of a short, fault or overload. It poses a danger for servicing personnel if you still have a hot conductor in a MWBC box. Whether that be a junction box or an outlet box... whatever.
Eh... It's code. NEC 210.4(B)
does anyone have any input as to how that plug adapter looks that i posted up?
A simple pony panel can be made, a small 4 breaker breaker box is wired up to feed 4 new circuits all protected with there own breakers. This pony panel plugs into the dryer plug. I use them all day long on sites, I have 5 made now and am having another 5 made up by the electrician.